Paraguay grid — Yguazú transmission failure triggers nationwide blackout
18 February 2026 · Began at 15:18
Yguazú, Alto Paraná, Paraguay (substation marker approximate)
Map
-25.4178, -55.1002
What happened
A connector on one phase of the 500 kV potential transformer associated with Yguazú Substation's 500/220 kV T01 transformer detached during an afternoon of extreme heat. According to ANDE's later technical account, that initial fault caused protection systems to disconnect both 220 kV Yguazú–Coronel Oviedo transmission lines. With insufficient redundant transmission capacity, voltage fell, sensitive loads disconnected and the generation-demand imbalance separated the systems supplied by Itaipu, Yacyretá and Acaray. The reduced load then produced an overvoltage that tripped protection at Itaipu's Margen Derecha substation, leaving the Itaipu- and Acaray-supplied system without service. Itaipu said its generating plant and substation had operated normally and that the initiating event was external to the utility. The outage affected about five million people amid heat indices reported around 45–49°C, disrupted traffic signals and threatened water-pumping operations. This is the power-grid companion to the communications-layer record for the same 18 February blackout; it is not a second event. Early coverage published on 19 February described two 500 kV lines, but ANDE's subsequent technical report identified one detached 500 kV connector followed by the loss of two 220 kV lines.
When cited sources give different casualty, damage or spill figures for this event, they’re reported side by side above rather than merged into one number. See how confidence levels work.
- Evidence
- Documented
- Confidence
- High
- Infrastructure
- Power Grid
- Current temperature
- Loading…
- Latitude
- -25.4178°
- Longitude
- -55.1002°
Attribution
Responsibility has not been established in the cited reporting.
Sources
- ANDE revela la secuencia de cortes que provocó el apagón que afectó a 5 millones de personasÚltima Hora · Incident reporting
- Fuera de servicio ocurrió por actuación de protecciones ante magnitud eléctrica que superó límites permitidosAgencia IP · Paraguayan state news account of ANDE's technical findings and transmission-redundancy assessment
- Itaipú deslinda responsabilidad del corte de luz a nivel paísDiario HOY · Itaipu statement that its plant and Margen Derecha substation operated normally
- Apagão no Paraguai entra em fase de normalizaçãoCanal Solar · Early restoration coverage published on 19 February; its initial voltage description was superseded by ANDE's later technical report